AL600ULM

Access Power Distribution Module w/ Power Supply/Charger, 5 PTC Class 2 Outputs, 12/24VDC @ 6A, FAI, 115VAC, BC300 Enclosure

AL600ULM multi-output access control power supply/charger is specifically designed for use with access control systems and accessories. This unit converts a 115VAC, 60Hz input into five (5) individually protected Class 2 Rated power limited 12VDC or 24VDC outputs. Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form "C" dry output relay enables HVAC Shutdown, Elevator Recall or it may be used to trigger auxiliary devices.

  • Input
    • Input 115VAC, 60Hz, 3.5A.
    • Input fuse rated @ 3.5A/250V.
    • Fire Alarm Panel or Access Control System trigger inputs. N.O. or N.C.supervised trigger input and polarity reversal trigger input.
  • Output
    • 12VDC or 24VDC selectable outputs.
    • 6A supply current.
    • Five (5) PTC protected Class 2 Rated power limited outputs, rated @ 2A (auto-resettable).
    • Output relay energizes when unit is triggered (form "C" contact rated 1A @ 28VDC).
    • Filtered and electronically regulated output.
    • Short circuit and thermal overload protection.
  • Battery Backup
    • Built-in charger for sealed lead acid or gel type batteries.
    • Automatic switch over to stand-by battery when AC fails.
    • Zero voltage drop when switching over to battery backup.
    • (Batteries are sold separately).
  • Supervision
    • AC fail supervision (form "C" contacts).
    • Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
    • Low battery supervision (form "C" contacts).
    • Battery presence supervision (form "C" contacts).
    • Power fail supervision relay (form "C" contacts).
  • Visual Indicators
    • AC input and DC output LED indicators (power supply board).
    • Red LEDs indicate condition of power outputs (multi-output board).
    • Power & input trigger LEDs (multi-output board).
  • Temperature
    • Operating: 0° C to 49° C (32° F to 120° F).
    • Storage: - 20° C to 70° C ( - 4° F to 158° F).
    • Relative Humidity 85% +/- 5%.
      • BTU/Hr (approx.):
        • 12VDC: 37 BTU/Hr.
        • 24VDC: 74 BTU/Hr.
    • System AC input VA requirement: 166.75VA.
UL Listed For:
Access Control System Units (UL294)
Power Supplies for Fire Protective Signaling Systems (UL1481)
Power Supplies for use with Burglar Alarm Systems (UL603)
Hospital Signaling and Nurse Call Equipment (UL1069)
cUL Listed For:
CSA Standard C22.2 No.205-M1983, Signal Equipment
 
CSFM - California State Fire Marshal Approved
 
MEA - NYC Department of Buildings Approved
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to two (2) 12VDC/7AH Batteries.
  • Dimensions 13"W x 13.5"H x 3.25"D (330 mm W x 343 mm H x 83 mm D).
  • 1/2" and 3/4" combination knockouts.
Weights (approximate):
  • Product Weight: 7.9 Lbs. (3.583 kg).