Specifications
Input
- Nominal 220VAC (working range 198VAC-256VAC), 50/60Hz, 2.5A.
- Input fuse rated @ 3.5A/250V.
Output
- 24VDC output.
- 10A of continuous supply current for Access Control applications.
- 8A of continuous supply current for Fire Alarm applications.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Battery Backup
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switch over to stand-by battery when AC fails.
- Zero voltage drop when switched over to battery backup.
- (Batteries are sold separately).
Supervision
- AC fail supervision (form "C" contacts).
- Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
- Low battery supervision (form "C" contacts).
- Battery presence supervision (form "C" contacts).
Visual Indicators
- AC input and DC output LED indicators.
Electrical
Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity 85% +/- 5%.
- BTU/Hr (approx.): 123 BTU/Hr.
- System AC input VA requirement: 550VA.
Dimensions & Weight
Dimensions (approximate):
- 4.5"W x 8.4"L x 1.4"H (114.4 mm W x 213.4 mm L x 35.6 mm H).
Weights (approximate):
- Product Weigtht: 1.15 Lbs. (0.52 kg).
- Shipping Weigtht: 1.45 Lbs. (0.66 kg).