Specifications
Input
Output
- 12VDC or 24VDC selectable output.
- 6A supply current.
- Filtered and electronically regulated outputs.
- Short circuit and thermal overload protection.
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current 0.7A.
- Zero voltage drop when switching over to battery backup.
- (Batteries are sold separately).
Supervision
- AC fail supervision (form "C" contacts).
- Battery presence and low battery supervision (form "C" contacts).
Visual Indicators
- AC input and DC output LED indicators.
Electrical
Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
- 12VDC: 37 BTU/Hr.
- 24VDC: 75 BTU/Hr.
- System AC input VA requirement: 184VA.
Dimensions & Weight
Dimensions (approximate):
- 7.045"W x 4.266"L x 2.127"H (178.95 mm W x 108.36 mm L x 54.05 mm H).
Weights (approximate):
- Product Weigtht: 0.55 Lbs. (0.25 kg).
- Shipping Weigtht: 0.7 Lbs. (0.32 kg).