T2KHK312D

12-Door Altronix/Kantech Access and Power Integration Kit - Trove2KH2 with AL600ULXB, T1618300K, ACM4CB, ACM8CB

Altronix T2KHK312D kit consists of Trove2 enclosure, TKH2 Kantech/Altronix backplane with one (1) 12VDC or 24VDC @ 6A power supply/charger, one (1) eight (8) output PTC access power controller, one (1) four (4) output PTC access power controller and one (1) 16VAC/18VAC transformer.
This kit also accommodate various combinations of Kantech boards for up to twelve (12) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

Specifications

  • AL600ULXB Power Supply/Charger
      • Input
        • Voltage: 115VAC, 60Hz, 3.5A max.
        • Fusing: 5A / 250V.
      • Outputs
        • Voltage: 12VDC or 24VDC selectable.
        • Current: 6A @ 12VDC or 24VDC continuous max.
        • Filtered and regulated.
  • Battery Charging
    • Capacity: 7AH / 12VDC (up to 4 within enclosure); 12AH / 12VDC (up to 4 within enclosure); 40 AH / 65 AH (requires separate enclosure)
    • Type: Sealed lead acid or gel type
    • Failover: Upon AC loss, instantaneous
    • (Batteries are sold separately).
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
  • Indicators LED
    • Input: 115VAC is present.
    • DC Output: Powered.
    • Battery: Discharged or not connected.
  • ACM4CB Access Power Controller
      • Input
        • 24VDC from AL600ULXB.
        • Input Fuse: 10A / 32V.
      • Outputs
        • Voltage: 24VDC.
        • Four (4) independently controlled 2A outputs:
        • a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
        • b) Any combination of the above.
        • Four (4) auxiliary power outputs (unswitched).
      • Outputs Ratings
        • PTCs: 2A.
      • Indicators (LED)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • ACM8CB Access Power Controller
      • Input
        • Voltage: 24VDC from AL600ULXB.
        • Main Fuse: 10A / 250V.
      • Outputs
        • Voltage: 24VDC.
        • Eight (8) 24VDC independently controlled fused outputs:
        • a) Fail-Safe and/or Fail-Secure power outputs.
        • b) Any combination of the above.
        • Output PTCs: 2.5A.
      • Indicators (LED)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • T1618300K Transformer
      • Input
        • Voltage: 115VAC, 50/60Hz, 2.7A.
      • Output
        • Voltage: 16VAC/300VA (18.7A) or 18VAC/300VA (16.7A).
  • Environmental
      • Temperature
        • Operating: 0° C to 50° C (32° F to 122° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 232 BTU/Hr.

Agency Listings

 
CE Compliant

Accessories

Name Description
MM12 Mounting Magnets, Twelve (12) Quantity per Pack
MM24 Mounting Magnets, Twenty Four (24) Quantity per Pack
MM4 Mounting Magnets, Four (4) Quantity per Pack
MM8 Mounting Magnets, Eight (8) Quantity per Pack
WM100 Magnetic Cable Tie Mounts
WM25 Magnetic Cable Tie Mounts
WM5 Magnetic Cable Tie Mounts

Dimensions & Weight

Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 21.5"W x 27.25"H x 6.5"D (546.1 mm W x 692.15 mm H x 165.1 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weigtht: 61.7 Lbs. (28 kg).
  • Shipping Weigtht: 66.7 Lbs. (30.25 kg).