16-Door Altronix/Mercury Access and Power Integration Kit - Trove2M2 and TMV2 door backplane with eFlow104NB, eFlow102NB, (2) LINQ8ACMCB, PDS16CB. Trove2 Series

Altronix T2MK75F16ADQ kit consists of Trove2 enclosure, TM2 Mercury/Altronix backplane and TMV2 door backplane with one (1) 24VDC @ 10A and one (1) 12VDC @ 10A power supply/chargers, two (2) eight (8) PTC protected output dual input/output network access control modules and one (1) sixteen (16) PTC protected dual input/output power distribution module. This kit also accommodates various combinations of Mercury/Lenel* boards for up to sixteen (16) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

*Also compatible with these authentic Mercury partners:
AccessNsite, Avigilon, BadgePass, BluBox, Feenics, Genetec, Identicard, IMRON, Johnson Controls, Kastle, Keri Systems, Lenel/S2, LockState, Maxxess, Midpoint Security, NLSS, Open Options, Panasonic Video Insight, Quintron, RS2, Schneider Electric, Vanderbilt

Specifications

  • eFlow104NB Power Supply/Charger - 1
      • Input
        • Voltage: 120VAC, 60Hz, 4.5A
        • Main Fuse: 6.3A / 250V.
      • Output
        • Voltage: 24VDC @ 10A.
        • Auxiliary: 1A (unswitched).
        • Other: Overvoltage protection. Filtered and regulated.
  • eFlow102NB Power Supply/Charger - 2
      • Input
        • Voltage: 120VAC, 60Hz, 3.5A.
        • Main Fuse: 5A / 250V.
      • Output
        • Voltage: 12VDC @ 10A.
        • Auxiliary: 1A (unswitched).
        • Other: Overvoltage protection. Filtered and regulated.
  • Both Power Supplies
      • Battery Charging
        • Capacity: 12VDC/12AH (4 within enclosure); 40AH/65AH (requires separate enclosure)
        • Type: Sealed lead acid or gel type
        • Failover: Upon AC loss, instantaneous
        • (Batteries are sold separately).
      • Fire Alarm Disconnect
        • Supervised: Latching or non-latching.
        • EOL: 10K Resistor.
      • Supervision
        • AC Failure: Form “C” contacts.
        • Battery: Form “C” contacts.
        • Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
      • Indicators LED
        • AC Input: 120VAC is present.
        • DC Output: Powered.
        • Battery: Discharged or not connected.
  • PDS16CB Dual Input Power Distribution Module
      • Input
        • Voltage: 24VDC from eFlow104NB and 12VDC from eFlow102NB.
        • Input PTCs: 9A.
      • Outputs
        • Voltage: 12VDC and/or 24VDC.
        • Any of the sixteen (16) power outputs are selectable to follow power Input 1 or Input 2
        • Individual outputs may be set to OFF position for servicing.
      • Outputs Ratings
        • PTC: 2.5A.
      • Indicators (LED)
        • DC Output: Sixteen (16) individual output LEDs.
        • Green: 12VDC.
        • Red: 24VDC.
  • Two (2) LINQ8ACMCB Networked Access Power Controllers
      • Input
        • Voltage: 24VDC from eFlow104NB and 12VDC from eFlow102NB
        • Input PTCs: 9A
      • Outputs
        • PTC protected outputs
        • Any of the eight (8) PTC protected power outputs are selectable to follow power Input 1 or Input 2
        • Individual outputs may be set to OFF position for servicing
      • Output PTCs:
        • 2.5A
  • Programming Features:
      • Eight (8) Programmable Outputs:
        • - Fail-safe, fail-secure or auxiliary outputs
        • - Input controlled or manually controlled through software
        • - High (over) and low (under) voltage and current monitoring by output
        • - Multiple outputs may be programmed to be triggered by a single input
        • - Battery back-up by output
      • Eight (8) Programmable Trigger Inputs:
        • - Normally open (NO), Normally closed (NC) or Open collector sink inputs
        • - Wet Input (5VDC - 24VDC) with 10k resistor
        • - Any combination of the above
      • Other Programmable Trigger Inputs:
        • - Monitor power supply(ies) input for voltage and current limits (high/low)
        • - Input and output current calibration, Programmable timer events
        • - Programmable user levels, Enable or disable alerts by type
        • - Programmable alert reporting delay
      • Indicators (LED)
        • Green AC LED: indicates AC trouble condition
        • Green BAT LED: indicates battery trouble condition
        • Green FACP LED: indicates FACP disconnect is triggered
        • Flashing Blue Heartbeat LED: indicates network connection
        • Individual OUT1 - OUT8 Red LEDs: indicate outputs are triggered
        • Individual Voltage LEDs: indicate 12VDC (Green) or 24VDC (Red)
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 217 BTU/Hr.

Agency Listings

 
CE Compliant

Accessories

Name Description
WM5 Magnetic Cable Tie Mounts
WM25 Magnetic Cable Tie Mounts
WM100 Magnetic Cable Tie Mounts
MM4 Mounting Magnets, Four (4) Quantity per Pack
MM8 Mounting Magnets, Eight (8) Quantity per Pack
MM12 Mounting Magnets, Twelve (12) Quantity per Pack
MM24 Mounting Magnets, Twenty Four (24) Quantity per Pack
BR1 Add-On Mounting Bracket
Trove2BWC Battery/Wire Trough Enclosure

Dimensions & Weight

Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 21.5"W x 27.25"H x 6.5"D (546.1 mm W x 692.15 mm H x 165.1 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weigtht: 49 Lbs. (22.23 kg).
  • Shipping Weigtht: 53.35 Lbs. (24.2 kg).