T2MK75F16DQV

16-Door Altronix/Mercury Access and Power Integration Kit - Trove2M2 and TMV2 door backplane with eFlow104NBV, LINQ2, (2) ACM8CB, PDS16WCB

Altronix T2MK75F16DQV kit consists of Trove2 enclosure, TM2 Altronix/Mercury backplane and TMV2 door backplane with 24VDC @ 10A and 12VDC @ 10A power supply/chargers, Network communication module, sixteen (16) PTC protected output power distribution module and two eight (8) PTC protected output access control modules. This kit also accommodates various combinations of Mercury* boards for up to eight (8) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

*Also compatible with these authentic Mercury partners: AccessNsite, Avigilon, BadgePass, BluBox, Feenics, Genetec, Identicard, IMRON, Johnson Controls, Kastle, Keri Systems, Lenel/S2, LockState, Maxxess, Midpoint Security, NLSS, Open Options, Panasonic Video Insight, Quintron, RS2, Schneider Electric, Vanderbilt

Specifications

  • eFlow104NBV Power Supply/Charger - 1
      • Input
        • Voltage: 220VAC (working range 198VAC - 256VAC), 50/60Hz, 2.7A.
        • Main Fuse: 6.5A / 250V.
      • Outputs
        • Voltage: 24VDC @ 10A.
        • Auxiliary: 1A (unswitched).
        • Protection: Overvoltage protection. Filtered and regulated.
  • eFlow102NBV Power Supply/Charger - 2
      • Input
        • Voltage: 220VAC (working range 198VAC - 256VAC), 50/60Hz, 2.1A.
        • Input Fuse: 5A / 250V.
      • Output
        • Voltage: 12VDC @ 10A.
        • Auxiliary: 1A (unswitched).
        • Protection: Overvoltage protection. Filtered and regulated.
  • Both Power Supplies
      • Battery Charging
        • Capacity: 12VDC/12AH (4 within enclosure); 40AH/65AH (requires separate enclosure).
        • Type: Sealed lead acid or gel type.
        • Failover: Upon AC loss, instantaneous.
        • (Batteries are sold separately).
      • Fire Alarm Disconnect
        • Supervised: Latching or non-latching.
        • EOL 10K Resistor.
      • Supervision
        • AC Failure: Form “C” contacts.
        • Battery: Form “C” contacts.
        • Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
      • Indicators LED
        • AC Input: 220VAC is present
        • DC Output: Powered
        • Battery: Discharged or not connected
  • LINQ2 Network Communication Module
      • Status Monitoring
        • AC status; Output current draw; Unit’s temperature;
        • DC output voltage; Low Battery/Battery presence detection.
        • Input trigger state change; Output (relay and power supply) state change
      • Programming
        • Battery service date indication
        • Programmable via USB or web browser
        • Automated timed events:
        • - Control output relays and power supply via flexible timing parameter
      • Reporting
        • Programmable dashboard notifications
        • E-mail notification selectable by event
        • Event log tracks history (100+ events)
      • Indicators (LED)
        • Blue LED: Power ON
  • Two (2) ACM8CB Access Power Controllers
      • Input
        • Voltage: 24VDC from eFlow104NBV.
        • Main Fuse: 10A / 250V.
      • Outputs
        • Voltage: 24VDC.
        • Eight (8) 24VDC independently controlled PTC outputs:
        • a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
        • b) Auxiliary power outputs (unswitched).
        • c) Any combination of the above.
        • Output PTCs: 2.5A.
      • Indicators (LED)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • PD16WCB Power Distribution Module
      • Input
        • Voltage: 12VDC from eFlow102NBV
      • Outputs
        • Voltage: 12VDC
        • PTCs: 2.5A.
      • Indicators (LED)
        • Green LED: DC Output
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 217 BTU/Hr.

Agency Listings

 
CE Compliant

Accessories

Name Description
WM5 Magnetic Cable Tie Mounts
WM25 Magnetic Cable Tie Mounts
WM100 Magnetic Cable Tie Mounts
MM4 Mounting Magnets, Four (4) Quantity per Pack
MM8 Mounting Magnets, Eight (8) Quantity per Pack
MM12 Mounting Magnets, Twelve (12) Quantity per Pack
MM24 Mounting Magnets, Twenty Four (24) Quantity per Pack
BR1 Add-On Mounting Bracket
Trove2BWC Battery/Wire Trough Enclosure

Dimensions & Weight

Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 21.5"W x 27.25"H x 6.5"D (546.1 mm W x 692.15 mm H x 165.1 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weigtht: 50 Lbs. (22.68 kg).
  • Shipping Weigtht: 53.75 Lbs. (24.38 kg).