Maximal11FE

Power Supply/Charger, Expandable, Dual 12/24VDC outputs @ 3.5A each (12A max), 115VAC, FAI, LinQ2 Ready, BC800 Enclosure

Maximal11FE Expandable Power System provide system designers and installers with optimum power choices and the highest levels of versatility. They provide 12VDC, 24VDC, or 12VDC and 24VDC simultaneously via two (2) single output power supply/chargers. Includes AC fail, low battery and battery presence monitoring. Enclosure facilitates up to four (4) 12VDC/12AH batteries. All interconnecting equipment must be UL Listed.

  • Input
    • 120VAC 60Hz, 7.0A. input.
  • Output
    • 12VDC and/or 24VDC outputs.
      • Maximum output current Options:
        • A) 12VDC @ 4A. plus 12VDC @ 4A.
        • B) 24VDC @ 4A. plus 24VDC @ 4A.
        • C) 12VDC @ 4A. plus 24VDC @ 4A.
    • Power-limited outputs.
    • Aux. power-limited output rated @ 1A. (unswitched).
    • Over Voltage Protection.
  • Fuse Ratings
    • Power Supply input fuse rated @ 5A./250V.
  • Fire Alarm Disconnect
    • Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
  • Supervision
    • AC fail supervision (form "C" contacts).
    • Notification trigger is selectable for 30 seconds (factory set) or 2 hours.
    • Battery fail & presence supervision (form "C" contacts).
    • Low power shutdown. Prevents deep battery discharge.
  • Battery Backup
    • Built-in charger for sealed lead acid or gel type batteries.
    • Automatic switch over to stand-by battery when AC fails.
    • Battery fuse rated @ 7.5A./32V.
  • Visual Indicators
    • Green AC Power LED indicates 120VAC present.
    • AC input and DC output LED indicators.
  • Electrical
      • Temperature:
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
    • Relative Humidity 85% +/- 5%.
      • BTU/Hr (approx.):
        • 12VDC: 48 BTU/Hr.
        • 24VDC: 74 BTU/Hr.
        • 12VDC & 24VDC: 98 BTU/Hr.
    • System AC input VA requirement: 840VA.
UL Listed For:
Access Control System Units (UL294)
cUL Listed For:
CSA Standard C22.2 No.205-M1983, Signal Equipment
 
CSFM - California State Fire Marshal Approved
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 19"W x 27"H x 6.25"D (483 mm W x 685.8 mm H x 159 mm D).
  • 1/2" and 3/4" combination knockouts.
Weights (approximate):
  • Product Weigtht: 32.1 Lbs. (14.6 kg).
  • Shipping Weigtht: 39.25 Lbs. (17.8 kg).