T1CVK3F4

4-Door Altronix/CDVI Access and Power Integration Kit - Trove1C1 with eFlow6NB, ACM4

Altronix T1CVK3F4 kit consists of Trove1 enclosure, TC1 CDVI/Altronix backplane with one (1) 12 or 24VDC @ 6A power supply/charger and one (1) fused access power controller. This kit also accommodate various combinations of CDVI Atrium A22K/A22NB/ADH10 boards for up to four (4) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

  • eFlow6NB Power Supply/Charger
      • Input
        • Voltage: 120VAC, 60Hz, 3.5A max.
        • Fusing: 5A / 250V.
      • Outputs
        • Voltage: 12VDC or 24VDC selectable.
        • Current: 6A continuous max.
        • Auxiliary: Power-limited @ 1A (unswitched).
        • Other: Overvoltage protection. Filtered and regulated.
  • Battery Charging
    • Type: Sealed lead acid or gel type.
    • Fuse Rating: 10A @ 32VDC.
    • Failover: Upon AC loss, instantaneous.
    • (Batteries are sold separately).
  • Fire Alarm Disconnect
    • Supervised: Latching or non-latching.
    • EOL: 10K Resistor.
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
    • Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
  • Indicators LED
    • Input: 120VAC is present.
    • DC Output: Powered.
  • ACM4 Access Power Controller
      • Input
        • Voltage: 12VDC or 24VDC from eFlow6NB.
        • Main Fuse: 10A /32V.
      • Outputs
        • Voltage: 24VDC.
        • Four (4) independently controlled 2.5A outputs:
        • a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
        • b) Four (4) dry form “C” 5A rated relay outputs.
        • c) Any combination of the above.
        • Four (4) auxiliary power outputs (unswitched).
        • Output Fuses: 3A / 32VDC.
      • Indicators (LED)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • Environmental
      • Temperature
        • Operating: 0° C to 50° C (32° F to 122° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 12VDC: 40 BTU/Hr.
        • 24VDC: 77 BTU/Hr.
 
CE Compliant
 
Components of this Trove kit are UL Listed sub-assemblies. Please refer to the corresponding Sub-Assembly Installation Guides for further information. Sub-assembly components of this kit can be found under the "Kit Contents" tab.
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to two (2) 12VDC/7AH Batteries.
  • Dimensions 14.5"W x 18"H x 4.62"D (368.3 mm W x 457.2 mm H x 118 mm D).
  • 1", 3/4" and 1 1/2" knockouts.
Weights (approximate):
  • Product Weight: 15.5 Lbs. (7 kg).
  • Shipping Weight: 19.5 Lbs. (8.9 kg).
Print

Access controllers not included

*Batteries sold separately