T3SH775F24DPQ

24-Door Altronix/Software House Access and Power Integration Kit - Trove3SH3 with (2) eFlow104NB, eFlow102NB, (3) ACMS8CB, LINQ8PDCB, RSB1, RSB2

Altronix T3SH775F24DPQ kit consists of Trove3 enclosure and TSH3 Software House/Altronix backplane with two (2) 24VDC @ 10A and one (1) 12VDC @ 10A power supply/chargers, three (3) eight (8) PTC protected dual input access control modules and one (1) eight (8) PTC protected output managed power distribution module. This kit also accommodates various combinations of Software House boards for up to twenty-four (24) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

  • Two (2) eFlow104NB Power Supply/Chargers - 1 & 2
      • Input
        • Voltage: 120VAC, 60Hz, 4.5A max
        • Main Fuse: 6.5A / 250V.
      • Output
        • Voltage: 24VDC @ 10A.
        • Auxiliary: 1A (unswitched).
        • Other: Overvoltage protection. Filtered and regulated.
  • eFlow102NB Power Supply/Charger - 3
      • Input
        • Voltage: 120VAC, 60Hz, 3.5A max.
        • Main Fuse: 5A / 250V.
      • Output
        • Voltage: 12VDC @ 10A.
        • Auxiliary: 1A (unswitched).
        • Other: Overvoltage protection. Filtered and regulated.
  • All Power Supplies
      • Battery Charging
        • Capacity: 12VDC/12AH (4 within enclosure); 40AH/65AH (requires separate enclosure).
        • Type: Sealed lead acid or gel type.
        • Failover: Upon AC loss, instantaneous.
        • (Batteries are sold separately).
      • Fire Alarm Disconnect
        • Supervised: Latching or non-latching.
        • EOL: 10K Resistor.
      • Supervision
        • AC Failure: Form “C” contacts.
        • Battery: Form “C” contacts.
        • Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
      • Indicators LED
        • AC Input: 120VAC is present.
        • DC Output: Powered.
        • Battery: Discharged or not connected.
  • Three (3) ACMS8CB Dual Input Access Power Controllers
      • Input
        • Voltage: 24VDC from eFlow104NB and 12VDC from eFlow102NB.
        • Input PTC: 9A.
      • Outputs
        • Voltage: 12VDC or 24VDC individually selectable
        • Eight (8) selectable 12VDC - 24VDC independently controlled outputs or eight (8) independently controlled Form “C” relay outputs:
        • a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays. 28VAC or VDC @ 2.5A Rated.
        • b) Auxiliary power outputs (unswitched).
        • c) Any combination of the above.
        • Any of the eight (8) PTC protected power outputs are selectable to follow power Input 1 or Input 2
        • Individual outputs may be set to OFF position for servicing
      • Outputs Ratings
        • PTCs: 2.5A.
      • Indicators (LED)
        • Red LEDs: Outputs are triggered (relays energized)
        • Blue LED: FACP disconnect is triggered
        • Individual voltage LEDs:
        • Green: 12VDC
        • Red: 24VDC
  • LINQ8PDCB Network Power Distribution Module
      • Input
        • Voltage: 12VDC from eFlow102NB
        • Input Fuses: 15A/32V
      • Outputs
        • PTC protected auto-resettable outputs.
        • Any of the eight (8) PTC protected power outputs are selectable to follow power Input 1 or Input 2
        • Individual outputs may be set to OFF position for servicing
      • Output PTCs:
        • 2.5A
      • Status Monitoring
        • Power Supply output voltage and load, Voltage and load of each output
        • FACP trigger and reset status, Unit temperature (Celsius)
        • Power Supply AC and Battery status, Battery health
      • Reporting:
        • Windows Dashboard Alert messages
        • E-mail notifications, Event Log tracks history
      • Indicators (LED)
        • Bat Local: Charging current status
        • FACP: Triggered / Released
        • Input: Input signal
        • Out1 - Out8: Output status
  • Programming Features
    • Power Supply(ies) voltage and load limits (High/Low)
    • FACP trigger type (wet or dry-NO/NC)
    • Input Function (FACP reset/tamper)
    • Output Reset Trigger (NO/NC)
    • Battery Monitor Configuration:
    • - Battery condition (Low/Normal/Missing)
    • - Service Date
    • Configurable Output Relay(s).
    • Individual Output Configuration:
    • - Device ID
    • - Voltage and Current Limits (High/Low)
    • - FACP Trigger Setting (latching/non-latching/inactive)
    • - Battery Backup
  • Fire Alarm Interface
    • Supervised FACP disconnect (Latching or Non-Latching)
    • FACP reset (NC or NO)
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 265 BTU/Hr.
 
CE Compliant
 
Components of this Trove kit are UL Listed sub-assemblies. Please refer to the corresponding Sub-Assembly Installation Guides for further information. Sub-assembly components of this kit can be found under the "Kit Contents" tab.
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 30.12"W x 36.12"H x 7.06"D (768.1 mm W x 917.5 mm H x 179.3 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weight: 84.2 Lbs. (38.2 kg).
  • Shipping Weight: 97.5 Lbs. (44.22 kg).
Print

Access controllers not included

*Batteries sold separately