T2PHK77F24

24-Door Altronix/Openpath Access and Power Integration Kit with Fused Outputs - Trove2CV2 with Two (2) eFlow104NB, Three (3) ACM8. Trove2 Series

Altronix T2PHK77F24 kit consists of Trove2 enclosure, TCV2 Openpath/Altronix backplane with two (2) 24VDC @ 10A power supply/chargers, and three (3) eight (8) fuse protected output access control modules. This kit also accommodates up to one (1) Openpath Core, two (2) Elevator Board, three (3) 4-Port or 8-Port modules for up to sixteen (16) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

  • Two (2) eFlow104NB Power Supply/Chargers
      • Input
        • Voltage: 120VAC, 60Hz, 9A max.
        • Input Fuse: 6.3A / 250V.
      • Output
        • Voltage: 24VDC 10A.
        • Auxiliary: 1A (unswitched).
        • Protection: Overvoltage protection. Filtered and regulated.
  • Battery Charging
    • Capacity: 12VDC/12AH (2 within enclosure); 40 AH / 65 AH (requires separate enclosure)
    • Type: Sealed lead acid or gel type
    • Failover: Upon AC loss, instantaneous
    • (Batteries are sold separately).
  • Fire Alarm Disconnect
    • Supervised: Latching or non latching.
    • EOL: 10K Resistor.
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
    • Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
  • Indicators LED
    • AC Input: 120VAC is present.
    • DC Output: Powered.
    • Battery: Discharged or not connected.
  • Three (3) ACM8 Access Power Controllers
      • Input
        • Voltage: 24VDC from eFlow104NB.
        • Input Fuse: 10A / 250V.
      • Outputs
        • Voltage: 24VDC.
        • Eight (8) 24VDC independently controlled fused outputs:
        • a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
        • b) Auxiliary power outputs (unswitched).
        • c) Any combination of the above.
        • Output Fuses: 3.5A/250V.
      • Indicators (LED's)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 24VDC: 290 BTU/Hr.
        • 12VDC and 24VDC: 111 BTU/Hr.
 
CE Compliant
 
Components of this Trove kit are UL Listed sub-assemblies. Please refer to the corresponding Sub-Assembly Installation Guides for further information. Sub-assembly components of this kit can be found under the "Kit Contents" tab.
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 21.5"W x 27.25"H x 6.5"D (546.1 mm W x 692.15 mm H x 165.1 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weight: 49.8 Lbs. (22.59 kg).
  • Shipping Weight: 53.55 Lbs. (24.29 kg).
Print

Access controllers not included

*Batteries sold separately