T2PXK7F8DQ

8-Door Altronix/Paxton Access and Power Integration Kit - Trove2PX2 with eFlow104NB, LINQ8ACMCB, VR6, LINQ8PD

Altronix T2PXK7F8DQ kit consists of Trove2 enclosure, TPX2 Paxton/Altronix backplane with one (1) 24VDC @ 10A power supply/charger, one (1) voltage regulator, one (1) networked PTC protected eight (8) output access power controller and one (1) networked PTC protected eight (8) dual output power distribution module. This kit also accommodates Paxton Net2 Plus or Paxton10 boards for up to eight (8) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

  • eFlow104NB Power Supply/Charger
      • Input
        • Voltage: 120VAC, 60Hz, 4.5A max.
        • Input Fuse: 6.5A / 250V.
      • Output
        • Voltage: 24VDC
        • Current: 10A continuous
        • Auxiliary: Class 2 power-limited @ 1A (unswitched)
        • Protection: Overvoltage protection. Filtered and regulated.
  • Battery Charging
    • Capacity: 12VDC/12AH (4 within enclosure); 40 AH / 65 AH (requires separate enclosure)
    • Type: Sealed lead acid or gel type
    • Failover: Upon AC loss, instantaneous
    • (Batteries are sold separately).
  • Fire Alarm Disconnect
    • Supervised: Latching or non-latching.
    • EOL: 10K Resistor.
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
    • Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units. Prevents deep battery discharge.
  • Indicators LED
    • Input: 120VAC is present.
    • DC Output: Powered.
  • LINQ8ACMCB Networked Access Power Controller
      • Input
        • Voltage: 24VDC from eFlow104NB and 12VDC from VR6
        • Input PTCs: 9A
      • Outputs
        • PTC protected outputs
        • Any of the eight (8) PTC protected power outputs are selectable to follow power Input 1 or Input 2
        • Individual outputs may be set to OFF position for servicing
      • Output PTCs:
        • 2.5A
  • Programming Features:
      • Eight (8) Programmable Outputs:
        • - Fail-safe, fail-secure or auxiliary outputs
        • - Input controlled or manually controlled through software
        • - High (over) and low (under) voltage and current monitoring by output
        • - Multiple outputs may be programmed to be triggered by a single input
        • - Battery back-up by output
      • Eight (8) Programmable Trigger Inputs:
        • - Normally open (NO), Normally closed (NC) or Open collector sink inputs
        • - Wet Input (5VDC - 24VDC) with 10k resistor
        • - Any combination of the above
      • Other Programmable Trigger Inputs:
        • - Monitor power supply(ies) input for voltage and current limits (high/low)
        • - Input and output current calibration, Programmable timer events
        • - Programmable user levels, Enable or disable alerts by type
        • - Programmable alert reporting delay
      • Indicators (LED)
        • Green AC LED: indicates AC trouble condition
        • Green BAT LED: indicates battery trouble condition
        • Green FACP LED: indicates FACP disconnect is triggered
        • Flashing Blue Heartbeat LED: indicates network connection
        • Individual OUT1 - OUT8 Red LEDs: indicate outputs are triggered
        • Individual Voltage LEDs: indicate 12VDC (Green) or 24VDC (Red)
  • LINQ8PDCB Network Power Distribution Module
      • Input
        • Voltage: 24VDC from eFlow104NB and 12VDC from VR6
        • Input Fuses: 15A/32V
      • Outputs
        • PTC protected auto-resettable outputs.
        • Any of the eight (8) PTC protected power outputs are selectable to follow power Input 1 or Input 2
        • Individual outputs may be set to OFF position for servicing
      • Output PTCs:
        • 2.5A
      • Status Monitoring
        • Power Supply output voltage and load, Voltage and load of each output
        • FACP trigger and reset status, Unit temperature (Celsius)
        • Power Supply AC and Battery status, Battery health
      • Reporting:
        • Windows Dashboard Alert messages
        • E-mail notifications, Event Log tracks history
      • Indicators (LED)
        • Bat Local: Charging current status
        • FACP: Triggered / Released
        • Input: Input signal
        • Out1 - Out8: Output status
  • VR6 Voltage Regulator
      • Input
        • Voltage: 24VDC from eFlow104NB
      • Output
        • Voltage: 12VDC
        • Current: 6A continuous
        • Other: Surge suppression.
      • Indicators LED
        • Input: 24VDC is present
        • Output: Powered
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 128 BTU/Hr.
 
CE Compliant
 
Components of this Trove kit are UL Listed sub-assemblies. Please refer to the corresponding Sub-Assembly Installation Guides for further information. Sub-assembly components of this kit can be found under the "Kit Contents" tab.
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 21.5"W x 27.25"H x 6.5"D (546.1 mm W x 692.15 mm H x 165.1 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weight: 51.5 Lbs. (23.36 kg).
  • Shipping Weight: 54.5 Lbs. (24.72 kg).
Print

Access controllers not included

*Batteries sold separately