AL1024NKA8

Dual Voltage Access Power Controller with Power Supply/Charger, BC400 Encloshure

Ordering # AL1024NKA8 Kit Contents: AL1024ULXB2 with VR6 and ACMS8 UL Listed Sub-assemblies

Altronix AL1024NKA8 sub-assembly kit converts a 115VAC 60Hz input into eight (8) fuse protected outputs. Outputs are individually selectable, providing 12VDC or 5VDC up to 6A and/or 24VDC up to 10A (240W total power) for access control panels, door locks, and ancillary devices. Power outputs can be converted to dry form “C” contacts. Outputs are activated by an open collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. AL1024NKA8 will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs. The spade connectors allow you to daisy chain power to multiple ACMS8 modules. This feature allows you to distribute the power over more outputs for larger systems.

  • AL1024ULXB2 Power Supply/Charger
      • Input
        • Voltage: 115VAC, 60Hz, 4.2A max.
        • Input Fuse: 5A / 250V.
      • Outputs
        • Voltage: 24VDC.
        • Current: 10A @ 24VDC continuous max.
        • Protection: Overvoltage protection. Filtered and regulated.
  • Battery Charging
    • Capacity: 12AH /12VDC (2 within enclosure); 40 AH / 65 AH (requires separate enclosure).
    • Type: Sealed lead acid or gel type.
    • Failover: Upon AC loss, instantaneous.
    • (Batteries are sold separately).
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
  • Indicators LED
    • Input: 115VAC is present.
    • DC Output: Powered.
    • Battery: Discharged or not connected.
  • ACMS8 Dual Input Access Power Controller
      • Input
        • Voltage: 12 or 24VDC individually selectable.
        • Eight (8) selectable 12VDC or 24VDC independently controlled outputs or eight (8) independently controlled Form “C” relay outputs:
        • a) Fail-Safe and/or Fail-Secure power outputs.
        • b) Form “C” Relays. 28VAC or VDC @ 2.5A Rated.
        • c) Auxiliary power outputs (unswitched).
        • d) Any combination of the above.
        • Any of the eight (8) fuse protected power outputs are selectable to follow power Input 1 or Input 2.
        • Individual outputs may be set to OFF position for servicing.
        • Output Fuses: 3A/32V.
      • Indicators (LED)
        • Red LEDs: Outputs are triggered (relays energized).
        • Blue LED: FACP disconnect is triggered.
        • Out1 - Out8: Bi-colored LEDs indicate 12 or 24VDC.
  • VR6 Voltage Regulator
      • Input
        • Voltage: 24VDC from AL1024ULXB2.
      • Output
        • Voltage: 12VDC.
        • Current: 6A continuous.
        • Other: Surge suppression.
      • Indicators LED
        • Input: 24VDC is present.
        • Output: Powered.
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 123 BTU/Hr.
 
CE Compliant
 
Components of this kit are UL Listed sub-assemblies. Please refer to the corresponding Sub-Assembly Installation Guides for further information. Sub-assembly components of this kit can be found under the "Kit Contents" tab.
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to two (2) 12VDC/12AH Batteries.
  • Dimensions 12"W x 15.5"H x 4.5"D (304.8 mm W x 393.7 mm H x 114.3 mm D).
  • 1.125" and 1.375" combination knockouts.
Weights (approximate):
  • Product Weight: 9.4 Lbs. (4.26 kg).
  • Shipping Weight: 10.5 Lbs. (4.76 kg).
Print